3006241 NFO Quick guide

 

Quick installation guide 

for motor operation with analogue set point 

  

 

For full instructions please see the Operating and installation manual.

 

 

1. Connection of power supply and motor  

See

 Safety Aspects 

and

 Installation and Ventilation 

 

Connect the power cable’s phase conductors to terminals L1, L2 and L3 in the 
inverter. The earth must be connected to PE. See Recommended fuses. 

 

Connect the motor cable to terminals U, V and W in the inverter. The earth is 
connected to PE. Note if motor is Y or D-connected. A 400V Y/ 230V D motor must 
be Y-connected and a 690V Y/400V D must be D-connected. 

 

Any thermo contact or thermistor should be connected to terminals 25 and 21. A 
resistance of 10 k

, min 1/4W, must also be connected between terminals 25 and 

20. 

2. Connecting control signals 

 

Connect the analogue control signal to terminal 3 and ground reference to terminal 
23 for set point 0/2-10 V, or terminals 10 and 2 for set point 0/4-20 mA. 

 

Close terminals 5 and 1 for the start/run signal. 

 

The main alarm signal is connected to the fault relay output, terminals 8, 17 and 
28.  Terminals 17 and 28 are closed upon alarm.  

 

Any run indicator is connected to terminals 7, 16 and 27.  Terminals 16 and 7 are 
closed during operation. 

 

The factory setting for the inverter’s set point is 0-10 V.  To alter the set point, 
change the 

AinSet

 parameter as per table 7 in the user manual.

 

M

3~

U V W PE

L1 L2

L1

1

13

12

4

3

10

C

u

rr

e

n

t i

n

pu

t, 

0/

4

-20

m

A

Pot

en

tio

m

ete

r, 1

0

k

Vo

lta

g

e i

n

p

u

t, 0

/2

-1

0

V

R

u

n sig

n

al

 st

ar

t/

sto

p

Di

rect

ion

 o

f rot

a

tion

Fi

xe

d

 f

req

u

en

cy

 1

Fi

xed

 f

re

q

u

en

cy

 2

Fi

xes

 f

re

q

u

en

cy

 3

5 14 6 15 26

25

REV

PTC

FI

X1

FI

X2

FI

X3

RU

N

Fault relay/

alarm output

L3 PE

I/O ground

16 7

Run

indicator

27

Digital inputs

max 24V

+

-

8

28

17

L2 L3 PE

9 20

21

22

23

+24V

2

S3

+ -

S4

M

o

to

r sa

fe

ty

 t

h

e

rmi

sto

r (

PT

C

)

PT

C

 p

re

-c

o

n

ne

c

tio

n r

e

si

st

a

n

c

e

 1

0 k

24

VO

LT

AG

E

30

 

 

   

WARNING!  

If there is a run signal to the inverter (terminals 5 and 1 connected), the 

inverter will start at power up. This can be avoided by changing the 

AutoSt

 parameter.

     

 

Figure 1. Example of connection

 

Der tages forbehold for ændringer og rettelser

EXHAUSTO A/S
Odensevej 76
DK-5550 Langeskov

Tel. +45 65 66 12 34
Fax +45 65 66 11 10
[email protected]
www.exhausto.dk

GB

Содержание NFO Sinus G2

Страница 1: ...ignal The main alarm signal is connected to the fault relay output terminals 8 17 and 28 Terminals 17 and 28 are closed upon alarm Any run indicator is connected to terminals 7 16 and 27 Terminals 16...

Страница 2: ...gramming mode Check the motor s direction of rotation by pressing FWD motor rotates whilst the button is pressed If the motor moves in the wrong direction change two of the output motor phases on the...

Страница 3: ...ress PROG twice to exit the programming position Parameters For a complete parameter list see table 9 in the manual Checklist for parameter settings Parameter group Parameter Setting Own setting Comme...

Страница 4: ...e of inverter parts or its accessories will invalidate the inverter s guarantee Always contact NFO Drives AB if alterations or changes are necessary Please note The components in the power unit and ce...

Страница 5: ...2 til s tpunkt 0 4 20 mA Luk klemmerne 5 og 1 for start driftssignalet Hovedalarmsignalet er tilsluttet fejlrel ets udgang klemmerne 8 17 og 28 Klemme 17 og 28 lukkes ved alarm Driftsindikatorer tils...

Страница 6: ...e paremetergruppen to gange for at forlade programmeringstilstand Tryk S ST TO OP P for at bne lokal tilstand se Drift programmeringstilstand Kontroller motorens rotationsretning ved at trykke F FW WD...

Страница 7: ...ar ra am me et te er r I In nd ds st ti il ll li in ng g E Eg ge en n i in nd ds st ti il ll li in ng g K Ko om mm me en nt ta ar re er r b be es sk kr ri iv ve el ls se e Motor P Nom Indtast nominell...

Страница 8: ...es AB skal altid kontaktes hvis modificeringer eller ndringer er n dvendige Bem rk Komponenterne i kraftenheden og visse komponenter i signalenheden str mforsynes n r vekselretteren er tilsluttet str...

Страница 9: ...4 20 mA Velg terminal 5 og 1 for start kj r signal Hovedalarmsignalet kobles til feilrel uttaket terminal 8 17 og 28 Terminal 17 og 28 er lukket i alarmsituasjoner En eventuell driftsindikator kobles...

Страница 10: ...ruppen to ganger for g ut av programmodus Trykk p S ST TO OP P for g inn i lokal modus se Drifts Programmierngsmodus Kontroller motorens rotasjonsretning ved trykke p F FW WD D motoren roterer mens kn...

Страница 11: ...ekkliste for parameterinnstillinger Parametergruppe Parameter Innstilling Egen innstilling Kommentarer beskrivelse Motor P Nom Legg inn motordata se motorens merkeplate Motorens nominelle ytelse U Nom...

Страница 12: ...dig Ta alltid kontakt med NFO Drives AB hvis det er behov for endringer Merk f lgende Komponentene i kraftenheten og bestemte komponenter i signalenheten f r str m n r inverteren er koblet til str mfo...

Отзывы: