Page
69
AD-4410
11. Setting List
When performing maintenance, use the following list as a memorandum.
When making inquiries about the product, inform your local A&D dealer of the user settings.
11.1. Basic Functions
Function No.
Parameter or
Setting range
Description
Default
value
User
setting
F
fncf01
000000
to
111111
Disables key switch
0
: Does not disable the key switch function.
1
: Disables the key switch function.
000000
(binary)
fncf02
0
to
6
Assigns a function to the F key.
0
: None
1
: Manual print command
2
: Hold
3
: Alternate switch
4
: Momentary switch
5
: Clear the tare weight
6
: Clear the zero value
0
fncf03
1
to
3
Displays update rate
1
: 20 times/second
2
: 10 times/second
3
: 5 times/second
1
fncf04
0
to
13
Assigns a function to the
display.
0
: None
1
: Zero tracking in progress
2
: Alarm (Zero range setting error, over)
3
: F key status
4
: Near zero
5
: HI output (Over upper limit value)
6
: OK output (Within upper and lower limit values)
7
: LO output (Under lower limit value)
8
: User input 1
9
: User input 2
10
: User input 3
11
: User output 1
12
: User output 2
13
: User output 3
0
fncf05
0
to
16
Digital filter (cutoff frequency)
0
: None
1
: 11.0 Hz
2
: 8.0 Hz
3
: 5.6 Hz
4
: 4.0 Hz
5
: 2.8 Hz
6
: 2.0 Hz
7
: 1.4 Hz
8
: 1.0 Hz
8
Содержание AD-4410
Страница 1: ...AD 4410 Weighing Indicator INSTRUCTION MANUAL 1WMPD4002591...