2
An error occurred at conveyor
encoder 2.
Cable (defect), Module failure
(encoder)
Replace the encoder cable or encoder of the conveyor encoder 2.
3
An error occurred at conveyor
encoder 3.
Cable (defect), Module failure
(encoder)
Replace the encoder cable or encoder of the conveyor encoder 3.
1401
CANNOT CHANGE
CONVEYOR MODE
Input error
Do not switch "Encoder / Virtual encoder" with the general signal while
performing the conveyor synchronized function.
1402
WORK IN/NOT DATA
CNT. LMT. OVER
Work status error
Check the work in/not shift data and actual the work status within the shift area.
1403
WORK IN/NOT SHIFT
DATA POS LMT.
Work status error
Check the work in/not shift data and actual the work status within the shift area.
1404
WORK ID. DATA CNT.
LMT. OVER
Work status error
Check the work in/not shift data and actual the work status within the shift area.
1405
WORK ID. SHIFT DATA
POS LMT.
Work status error
Check the work in/not shift data and actual the work status within the shift area.
1406
START SHIFT DATA
CNT. LMT. OVER
Work status error
Check the work in/not shift data and actual the work status within the shift area.
1407
START SHIFT DATA POS
LMT.
Work status error
Check the work in/not shift data and actual the work status within the shift area.
1512
POWER SUPPLY FAN
ERROR
(SERVO)
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
Module failure
(converter)
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
Air inlet and exhaust
Check that the air inlet or outlet is not blocked.
1513
POWER SUPPLY
OVERHEAT
(SERVO)
The temperature rises in the
controller
Turn the power OFF then back ON after cooling the controller.
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
Module failure
(converter)
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy