9-202
1596
45-1
C
D
RE-CHO-A1
11
FS10
0
1081
In a file server task, request
mail data error detected.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
1082
IP address duplicated.
IP address setting error
(1)Reset the alarm, and then try again.
(2)The IP address is duplicated with the FS100 controller. Confirm the
IP address of the communication target.
(3)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
In a file server task, request
error occurred.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
1083
Failed in the endian
conversion.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
1084
In a file server task, receive
data area overflow.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
2045
In a RC connect management
task , send error detected.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
2046
Failed in the endian
conversion.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
2065
Detect RC server task send
error.
Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy
304 of 348