9-74
1596
45-1
C
D
RE-CHO-A1
11
FS10
0
16
PSTART instruction is the old
specification.
Setting error
(1)Check the following settings.
·The specifications of PSTART instruction
Register the PSTART instruction as new specification.
17
PWAIT instruction is the old
specification.
Setting error
(1)Check the following settings.
·The specifications of PWAIT instruction
Register the PWAIT instruction as new specification.
4104
WRONG EXECUTION
OF LOAD INST
Sub Code1 to 245: Signifies the
data transmission error.
Setting error
* Refer to the instruction manual for Data Transmission Function for details.
4105
WRONG EXECUTION
OF SAVE INST
Sub Code1 to 245: Signifies the
data transmission error.
Setting error
* Refer to the instruction manual for Data Transmission Function for details.
4106
WRONG EXECUTION
OF DELETE INST
Sub Code1 to 245: Signifies the
data transmission error.
Setting error
* Refer to the instruction manual for Data Transmission Function for details.
4107
OUT OF RANGE
(ABSO DATA)
Sub Code: Signifies the axis in
which the alarm occurred
Setting error
(1)Check the following settings.
·Move the manipulator or station to the zero position by the axis operation and
check the home position alignment marks (the arrow).
4112
DATA SENDING ERROR
1
Retry over of NAK
Communication error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
2
Retry over for timeout in timer A
Communication error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
3
Retry over for mutual response
error
Communication error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
4113
DATA RECEIVING
ERROR
1
Reception timeout (timer A)
Communication error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
2
Reception timeout (timer B)
Communication error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
3
Heading length is too short.
Setting error
(1)Reset the alarm.
(2)If the alarm occurs again, send EOT code to release the data link and then
check that the sending side data is correctly set.
(3)Check that the communication setting is correct.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy
176 of 348