Undefined symbols are included
in the application.
Setting error
Check that symbols such as undefined functions or constants, which are
provided from the system side, are included in the application program.
6
Load failure (other)
Setting error
(1)Check the definition of static variable in the MotoPlus application program is
correct or not.
(2)Check the MotoPlus application programs so that they are set within the
specified values.
(3)Check that the object files are appropriately created.
7
API library initialization failure
Setting error
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. If the alarm occurs again,
save the CMOS.BIN in maintenance mode, and then contact your YASKAWA
representative about occurrence status (operating procedure).
8
User root task not included
Setting error
Confirm that mpUsRoot() is described in the application program.
9
User root task generation failure
Setting error
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. IIf the alarm occurs
again, save the CMOS.BIN in maintenance mode, and then contact your
YASKAWA representative about occurrence status (operating procedure).
10
RAM-Disk generation failure
Setting error
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. If the alarm occurs again,
save the CMOS.BIN in maintenance mode, and then contact your YASKAWA
representative about occurrence status (operating procedure).
11
MotoPlus application process
generation failure
Setting error
Check that the object file is appropriately created.
12
application file "*.VXE" in the
controller exceeded the specified
value
Setting error
Set the number of application file "*.VXE" to be within the defined value. (Delete
unnecessary files from the MotoPlus menu of the maintenance mode.)
13
Failure to install the driver to
communicate between MotoPlus
application and the system.
Setting error
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. If the alarm occurs again,
save the CMOS.BIN in maintenance mode, and then contact your YASKAWA
representative about occurrence status (operating procedure).
1030
MEMORY ERROR
(PARAMETER FILE)
0
RCD, RCxG parameter error
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate parameter file in
maintenance mode, and then load the parameter file saved in the external
memory device.
Main CPU board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy