B70
Enable/Disable Immediate Callout and
80% Full Alarm
(Supervisor Mode Only)
Enables and configures the Immediate
Callout and 80% Full Alarm. When Immediate Callout is enabled,
NetLink will dial a user-defined Callout Number, approximately 5
seconds after a disconnect or loss of carrier. Note that the
Immediate Callout feature must be enabled prior to each use.
When the 80% Full Alarm is enabled, NetLink can perform any of
the standard Alarm Actions when internal memory becomes 80%
full. For more information, please refer to Section 10.
Command Options:
^B70
Disable Immediate Callout and 80% Full Alarm
^B70,I,1,1
Enable Immediate Callout
^B70,I,1,2
Disable Immediate Callout
^B70,I,2,n
Define Immediate Callout Number
(Where
n
= Desired Immediate Callout Number.)
^B70,I,2,
[Space]
Clear Immediate Callout Number.
^B70,%,1,1
Enable 80% Full Alarm.
^B70,%,1,2
Disable 80% Full Alarm.
^B70,%,2,x
Define notification action; Where
x
is the
desired action and
1
= None,
2
= Callout,
3
= Alphanumeric Page,
4
= Numeric Page,
5
= SNMP Trap,
6
= Output Contact Action, and
7
= Console Action.
^B70,%,3,n
Define number for 80% Full Callout or Page
(Where
n
is the desired phone number.)
^B70,%,3,
[Space]
Clear 80% Full callout number.
^B70,%,4,PagerID
Define Pager ID Number 1 for 80% Full Alarm.
^B70,%,4,
[Space]
Clear Pager ID Number 1.
^B70,%,5,PagerID
Define Pager ID Number 2 for 80% Full Alarm.
^B70,%,5,
[Space]
Clear Pager ID Number 2.
^B70,%,6,PagerID
Define Pager ID Number 3 for 80% Full Alarm.
^B70,%,6,
[Space]
Clear Pager ID Number 3.
^B70,%,7,message
Define 80% Full Alarm Message. This message can be
sent when the alarm generates a Callout, Alphanumeric
Page, SNMP Trap or Console Action.
^B70,%,7,
[Space]
Clear 80% Full Alarm Message.
^B70,%,8,1
Enable Auto Execute Function for 80% Full Alarm.
^B70,%,8,2
Disable Auto Execute Function for 80% Full Alarm.
^B70,%,9,cmds
Define the Auto Execute Command String for this
alarm. Where
cmds
is a series of ^Bxx commands,
with each command separated by a backslash character
followed by a forward slash (
\/
).
^B70,%,9,
[Space]
Clear Auto Execute Command String.
Corresponding Menu Function:
Immediate Callout; Modem Port
Configuration Menu, Item 34. 80% Full Alarm; Alarm
Configuration Menu, Item 5.