CLPU - Supervision Module Cold Load Pickup
Device planning parameters of the Cold Load Pickup module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
use
[Device planning]
Global protection parameter of the Cold Load Pickup-module
Parameter
Description
Setting range
Default
Menu path
Mode
Mode
CB POS,
I<,
CB POS Or I<,
CB POS And I<
CB POS
[Protection Para
/Global Prot Para
/CLPU]
ExBlo1
External blocking of
the module, if
blocking is activated
(allowed) within a
parameter set and if
the state of the
assigned signal is
true.
1..n, Assignment List -
[Protection Para
/Global Prot Para
/CLPU]
ExBlo2
External blocking of
the module, if
blocking is activated
(allowed) within a
parameter set and if
the state of the
assigned signal is
true.
1..n, Assignment List -
[Protection Para
/Global Prot Para
/CLPU]
Ex rev Interl
External blocking of
the module by
external reverse
interlocking, if
blocking is activated
(allowed) within a
parameter set and if
the state of the
assigned signal is
true.
1..n, Assignment List -
[Protection Para
/Global Prot Para
/CLPU]
CB Pos Detect
Criterion by which
the Circuit Breaker
Switch Position is to
be detected.
Only available if:
CLPU.Mode = I<
-.-,
CB.Pos
-
[Protection Para
/Global Prot Para
/CLPU]
Page 342
EN MRA4 04/09
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...