CLPU - Supervision Module Cold Load Pickup
CLPU - Supervision Module Cold Load Pickup
Available stages:
CLPU
This Supervision Module enables protection against faulty tripping of the Overcurrent Protection that might be
alarmed by the increased currents caused by the re-energizing after outages.
During normal operation the thermostatically load (refridgerators, heatings, residental air conditions) is
diversified. After an extended outage all these devices are switched on at the same time.
In addition to that motors evoke inrush currents when they are re-energized.
Both effects might cause an unwanted alarm/trip of the overcurrent protection stages.
If the
CPLU
-Module detects an Cold Load, the following countermeasures against unwanted tripping are
available.
•
Blocking of the Overcurrent Protection
•
Increase the tripping thresholds respectively the tripping times by means of Adaptive Parameters.
This Module issues a Signal only (it is not armed).
In order to take influence on the tripping settings of the overcurrent
protection you have to assign the signal „CPLU.E
FFEKTIVE
“ onto an Adaptive
Parameter Set. Please refer to chapter Parameter / Adaptive Parameter Sets.
Within the Adaptive Parameter Set you have to modify the tripping
characteristic of the overcurrent protection according to your needs.
EN MRA4 04/09
Page 339
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...