V-Protection Module – Voltage Protection [ANSI 27/59]
Parameter
Description
Setting range
Default
Menu path
V(t)<3
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
V[1]: 0.70Vn
V[2]: 0.70Vn
V[3]: 0.70Vn
V[4]: 0.30Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t3
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
0.15s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<4
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
V[1]: 0.70Vn
V[2]: 0.70Vn
V[3]: 0.70Vn
V[4]: 0.30Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t4
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
V[1]: 0.70s
V[2]: 0.70s
V[3]: 0.70s
V[4]: 0.6s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<5
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t5
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
1.50s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<6
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t6
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
3.00s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<7
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t7
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
3.00s
[Protection Para
/<n>
/V-Prot
/V[1]]
EN MRA4 04/09
Page 357
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...