V-Protection Module – Voltage Protection [ANSI 27/59]
Device Planning Parameters of the Voltage Protection Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
V>,
V<,
V(t)<
V[1]: V>
V[2]: V<
V[3]: V>
V[4]: V>
[Device planning]
Global Protection Parameters of the Voltage Protection Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of
the module, if
blocking is activated
(allowed) within a
parameter set and if
the state of the
assigned signal is
true.
1..n, Assignment List -
[Protection Para
/Global Prot Para
/V-Prot
/V[1]]
ExBlo2
External blocking of
the module, if
blocking is activated
(allowed) within a
parameter set and if
the state of the
assigned signal is
true.
1..n, Assignment List -
[Protection Para
/Global Prot Para
/V-Prot
/V[1]]
ExBlo TripCmd
External blocking of
the Trip Command
of the module/the
stage, if blocking is
activated (allowed)
within a parameter
set and if the state of
the assigned signal
is true.
1..n, Assignment List -
[Protection Para
/Global Prot Para
/V-Prot
/V[1]]
Page 354
EN MRA4 04/09
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...