Module: Trip Control (TripControl)
Trip Control Module Signals (Outputs States)
Name
Description
TripCmd
Signal: Trip Command
Res TripCmd Cr
Signal: Resetting of the Counter: total number of trip
commands
Ack TripCmd
Signal: Acknow TripCmd
Res Sum trip
Signal: Reset summation of the tripping currents
Pos
Signal: Circuit Breaker Position (0 = Indeterminate, 1 =
OFF, 2 = ON, 3 = Disturbed)
Ready
Signal: Circuit breaker is ready for operation.
Manual OFF
Signal: Circuit breaker was switched off manually.
Manual ON
Signal: Circuit breaker was switched on manually
Pos OFF
Signal: Circuit Breaker is in OFF-Position
Pos ON
Signal: Circuit Breaker is in ON-Position
Pos Indeterm
Signal: Circuit Breaker is in Indeterminate Position
Pos Disturb
Signal: Circuit Breaker Disturbed - Undefined Circuit
Breaker Position. The Position Indicators contradict
themselfes. After expiring of a supervision timer the
Position Indicators indicate that the circuit breaker is in
the ON and OFF-Position at the same time.
Trip Control Module – Sum of Tripping Currents
Value
Description
Menu path
Sum trip I L1
Summation of the tripping currents
phase1
[Operation
/Count and RevData
/CB]
Sum trip I L2
Summation of the tripping currents
phase2
[Operation
/Count and RevData
/CB]
Sum trip I L3
Summation of the tripping currents
phase3
[Operation
/Count and RevData
/CB]
Trip Control Module Values
Value
Description
Default
Size
Menu path
TripCmd Cr
Counter: Total
number of trips of
the switchgear
(circuit breaker, load
break switch…).
0
0 - 65535
[Operation
/Count and RevData
/CB]
EN MRA4 04/09
Page 259
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...