PF Protection Module – Power Factor [ANSI 55]
Parameter
Description
Setting range
Default
Menu path
Res Mode
Trigger Mode. Should the
Module be triggered if the
Current Pointer is leading to
the Voltage Pointer = Lead?
Or should the Module be
triggered if the Current
Pointer is lagging to the
Voltage Pointer = Lag?
leading,
lagging
leading
[Protection Para
/<n>
/PF-Prot
/PF[1]]
Reset Value
Reset Value
0.5 - 0.99
0.99
[Protection Para
/<n>
/PF-Prot
/PF[1]]
t
Tripping delay
0.00 - 300.00s
0.00s
[Protection Para
/<n>
/PF-Prot
/PF[1]]
Pre-trig Comp
Pre-trigger time for the
Compensation Signal.
When this timer is elapsed
the compensation signal will
be activated.
0.00 - 300.00s
5.00s
[Protection Para
/<n>
/PF-Prot
/PF[1]]
Post-trig Comp
Post-trigger time of the
Compensation Signal.
When this timer is elapsed
the compensation signal will
be deactivated.
0.00 - 300.00s
5.00s
[Protection Para
/<n>
/PF-Prot
/PF[1]]
Page 398
EN MRA4 04/09