ExP Protection Module – External Protection
Setting Group Parameters of the Module External Protection
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation
or deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/ExP
/ExP[1]]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection
parameter. If the
signal becomes true,
those
modules/stages are
blocked that are
parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/ExP
/ExP[1]]
Blo TripCmd
Permanent blocking
of the Trip
Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/ExP
/ExP[1]]
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection
parameter. If the
signal becomes true,
those
modules/stages are
blocked that are
parameterized
"ExBlo TripCmd
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/ExP
/ExP[1]]
Page 444
EN MRA4 04/09
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...