PF Protection Module – Power Factor [ANSI 55]
Parameter set parameters of the Power Factor module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/PF-Prot
/PF[1]]
ExBlo Fc
Activate (allow) or inactivate
(disallow) blocking of the
module/stage. This
parameter is only effective if
a signal is assigned to the
corresponding global
protection parameter. If the
signal becomes true, those
modules/stages are blocked
that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/PF-Prot
/PF[1]]
Blo TripCmd
Permanent blocking of the
Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/PF-Prot
/PF[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate
(disallow) blocking of the
module/stage. This
parameter is only effective if
a signal is assigned to the
corresponding global
protection parameter. If the
signal becomes true, those
modules/stages are blocked
that are parameterized
"ExBlo TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/PF-Prot
/PF[1]]
Trig Mode
Trigger Mode. Should the
Module be triggered if the
Current Pointer is leading to
the Voltage Pointer = Lead?
Or should the Module be
triggered if the Current
Pointer is lagging to the
Voltage Pointer = Lag?
leading,
lagging
lagging
[Protection Para
/<n>
/PF-Prot
/PF[1]]
Threshold
Alarm if the threshold is
exceeded
0.5 - 0.99
0.8
[Protection Para
/<n>
/PF-Prot
/PF[1]]
EN MRA4 04/09
Page 397
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...