Field Parameters
Field Parameters
Field Para
Within the field parameters you can set all parameters, that are relevant for the primary side and the mains
operational method like frequency, primary and secondary values and the star point treatment.
Parameter
Description
Setting range
Default
Menu path
Phase Sequence
Phase Sequence direction
ABC,
ACB
ABC
[Field Para]
f
Nominal frequency
50Hz,
60Hz
50Hz
[Field Para]
VT pri
Nominal voltage of the
Voltage Transformers at the
primary side
60 - 500000V
10000V
[Field Para]
VT sec
Nominal voltage of the
Voltage Transformers at the
secondary side.
60.00 - 400.00V 100V
[Field Para]
VT con
This parameter has to be set
in order to ensure the correct
assignment of the voltage
measurement channels in the
device.
Phase to Earth,
Phase to
Phase
Phase to Earth
[Field Para]
EVT pri
Primary nominal voltage of the
e-n winding of the voltage
transformers, which is only
taken into account in the
direct measurement of the
residual voltage (EVT
con=measured/open delta).
60 - 500000V
10000V
[Field Para]
EVT sec
Secondary nominal voltage of
the e-n winding of the voltage
transformers, which is only
taken into account in the
direct measurement of the
residual voltage (EVT
con=measured/open delta).
35.00 - 400.00V 100V
[Field Para]
EN MRA4 04/09
Page 229
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...