AR-Protection Module – Automatic Reclosure [ANSI 79]
Automatic Reclosure Module Values
Value
Description
Default
Size
Menu path
AR Shot No.
Counter - Auto
Reclosure Attempts
0
0 - 6
[Operation
/Count and RevData
/AR]
Total number Cr
Total number of all
executed Automatic
Reclosures Attempts
0
0 - 65536
[Operation
/Count and RevData
/AR]
Cr successfl
Total number of
successfully
executed Automatic
Reclosures
0
0 - 65536
[Operation
/Count and RevData
/AR]
Cr failed
Total number of
unsuccessfully
executed automatic
reclosure attempts
0
0 - 65536
[Operation
/Count and RevData
/AR]
AR Cr Alarm
Remaining numbers
of ARs until
Maintenance Alarm
1000
0 - 1000
[Operation
/Count and RevData
/AR]
AR Cr Block
Remaining numbers
of ARs until
Maintenance
Blocking
65536
0 - 65536
[Operation
/Count and RevData
/AR]
EN MRA4 04/09
Page 431
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...