V-Protection Module – Voltage Protection [ANSI 27/59]
Setting Group Parameters of the Voltage Protection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
V[1]: active
V[2]: active
V[3]: inactive
V[4]: inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only effective
if a signal is assigned to
the corresponding global
protection parameter. If
the signal becomes true,
those modules/stages are
blocked that are
parameterized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
Blo TripCmd
Permanent blocking of the
Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only effective
if a signal is assigned to
the corresponding global
protection parameter. If
the signal becomes true,
those modules/stages are
blocked that are
parameterized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
Meas Mode
Measuring/Supervision
Mode: Determines if the
phase-to-phase or phase-
to-earth voltages are to be
supervisioned
Phase to Earth,
Phase to Phase
Phase to Earth
[Protection Para
/<n>
/V-Prot
/V[1]]
Alarm Mode
Alarm criterion for the
voltage protection stage.
1-ph Trip,
3-ph Trip
1-ph Trip
[Protection Para
/<n>
/V-Prot
/V[1]]
EN MRA4 04/09
Page 355
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...