VE-Protection Module – Residual Voltage [ANSI 59N]
Setting Group Parameters of the Residual Voltage Supervision Module.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
ExBlo Fc
Activate (allow) or inactivate
(disallow) blocking of the
module/stage. This
parameter is only effective if
a signal is assigned to the
corresponding global
protection parameter. If the
signal becomes true, those
modules/stages are blocked
that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
Blo TripCmd
Permanent blocking of the
Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate
(disallow) blocking of the
module/stage. This
parameter is only effective if
a signal is assigned to the
corresponding global
protection parameter. If the
signal becomes true, those
modules/stages are blocked
that are parameterized
"ExBlo TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
VE>
If the pick-up value is
exceeded, the module/stage
will be started.
0.01 - 2.00Vn
1Vn
[Protection Para
/<n>
/V-Prot
/VE[1]]
t
Tripping delay
0.00 - 300.00s
0.00s
[Protection Para
/<n>
/V-Prot
/VE[1]]
EN MRA4 04/09
Page 365
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...