Module: Digital Inputs (DIs)
Optional Digital Inputs
DI Slot X6
Global Protection Parameters of the Optional Digital Inputs
Parameter
Description
Setting range
Default
Menu path
Nom voltage
Nominal voltage of
the digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X6
/Group 1]
Inverting 1
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X6
/Group 1]
Debouncing time 1
A change of the
state of a digital
input will only be
recognized after the
debouncing time has
expired (become
effective). Thus,
wipers will not be
misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X6
/Group 1]
Inverting 2
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X6
/Group 1]
Debouncing time 2
A change of the
state of a digital
input will only be
recognized after the
debouncing time has
expired (become
effective). Thus,
wipers will not be
misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X6
/Group 1]
Inverting 3
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X6
/Group 1]
EN MRA4 04/09
Page 133
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...