Device Parameters
Global Protection Parameters of the System
Parameter
Description
Setting range
Default
Menu path
PSet-Switch
Switching Parameter Set
PS1,
PS2,
PS3,
PS4,
PSS via Inp fct,
PSS via Scada
PS1
[Protection Para
/PSet-Switch]
PS1: activated by
This Setting Group will be
the active one if: The
Parameter Setting Group
Switch is set to "Switch via
Input" and the other three
input functions are inactive
at the same time. In case
that there is more than one
input function active, no
Parameter Setting Group
Switch will be executed. In
case all input functions are
inactive, the device will keep
working with the Setting
Group that was activated
lastly.
Only available if: PSet-
Switch = PSS via Inp fct
1..n, Assignment List -
[Protection Para
/PSet-Switch]
PS2: activated by
This Setting Group will be
the active one if: The
Parameter Setting Group
Switch is set to "Switch via
Input" and the other three
input functions are inactive
at the same time. In case
that there is more than one
input function active, no
Parameter Setting Group
Switch will be executed. In
case all input functions are
inactive, the device will keep
working with the Setting
Group that was activated
lastly.
Only available if: PSet-
Switch = PSS via Inp fct
1..n, Assignment List -
[Protection Para
/PSet-Switch]
EN MRA4 04/09
Page 477
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...