I-Protection Module – Overcurrent Protection [ANSI 50, 51, 67]
Parameter
Description
Setting range
Default
Menu path
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection
parameter. If the
signal becomes true,
those
modules/stages are
blocked that are
parameterized
"ExBlo TripCmd
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/I[1]]
I>
If the pick-up value is
exceeded, the
module/stage will be
started.
Only available if:
Characteristic =
DEFTOrCharacteristi
c = INV
0.01 - 40.00In
1.00In
[Protection Para
/<n>
/I-Prot
/I[1]]
Char
Characteristic
DEFT,
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T
DEFT
[Protection Para
/<n>
/I-Prot
/I[1]]
t
Tripping delay
Only available if:
Characteristic =
DEFT
0.00 - 300.00s
1.00s
[Protection Para
/<n>
/I-Prot
/I[1]]
Page 280
EN MRA4 04/09