Module: IEC60870-5-103
Spontaneous Events
The events that are generated by the device will be forwarded to the master with numbers for standard function
types / standard information. The data point list comprises all events that can be generated by the device.
Cyclic Measurement
The device generates on a cyclic base measured values by means of ASDU 9. They can be read out via a class
2 query. Please take into account that the measured values will be send out as multiples (1.2 or 2.4 times the
rated value). How to set 1.2 or 2.4 as multiplier for a value can be taken from the data point list.
The parameter “Transm priv meas val” defines if additional measurement values should be transmitted in the
private part. Public and private measured values are transmitted by ASDU9. That means that either a “private” or
a “public” ASDU9 will be transmitted. If this parameter is set, the ASDU9 will contain additional measured values
that are an enhancement of the standard. The “private” ASDU9 is send with a fixed function type and information
number that does not depend the type of device. Please refer to the data point list.
Commands
The data point list comprises a list of the supported commands. Any command will be responded by the device
with a positve or negative confirmation. If the command is executable, the execution with the corresponding
reason for the transmission (COT) will be lead in at first, and subsequently the execution will be confirmed with
COT1 within a ASDU9.
Disturbance Recording
The disturbances recorded by the device can be read out by means described in standard IEC60870-5-103.
The device is in compliance with the VDEW-Control System by transmission of an ASDU 23 without disturbance
records at the beginning of an GI-Cycle.
A disturbance record contains the following information:
•
Analog Measured Values, IL1, IL2, IL3, IN, Voltages VL1, VL2, VL3, VEN;
•
Binary States, transmitted as marks, eg Alarms and Trips.
•
Das Transmission ratio will not be supported. The transmission ratio is included in the “Multiplier”.
Blocking the Transmission Direction
The relay does not support functions to block the transmission in a certain direction (supervision direction).
EN MRA4 04/09
Page 211
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...