Smart View
Due to an bug in Windows 2000 it is possible that the automatically made
communication settings are not correctly adopted. In order to overcome
this problem, proceed as follows after setting up the serial connection:
•
Select menu point »Device Connection« in menu »Settings«.
•
Select »Serial Connection«.
•
Click button »Settings«.
•
Change to register card »General«.
•
Ensure that »Communication cable between two computers Com X
is selected in the »Drop Down Menu«. X = interface number where
you have connected the zero-modem cable to.
•
Click button »Configure«.
•
Ensure that the »Hardware Flowing Control« is activated.
•
Ensure that baud rate
»115200«
is selected.