AR-Protection Module – Automatic Reclosure [ANSI 79]
Setting Group Parameters of the Module Automatic Reclosure
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation
or deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/AR
/General settings]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection
parameter. If the
signal becomes true,
those
modules/stages are
blocked that are
parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/AR
/General settings]
Ex Sync
External
Synchronisation OK
inactive,
active
inactive
[Protection Para
/<n>
/AR
/General settings]
Attempts
Maximum number of
permitted reclosure
attempts.
1 - 6
1
[Protection Para
/<n>
/AR
/General settings]
t-start
Start timer - While
the start timer runs
down, an AR attempt
can be started. Only
if the trip command
is given within the
start time/duration an
AR attempt could be
started. The location
and the resistance of
the fault have a big
influence on the
tripping time. The
start time has an
impact on whether
an AR attempt
should be started
when the fault is far
away or high
resistance.
0.1 - 10.00s
1s
[Protection Para
/<n>
/AR
/General settings]
EN MRA4 04/09
Page 425
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...