Binary Output Relays
Global Protection Parameters of the Binary Output Relays
Parameter
Description
Setting range
Default
Menu path
t-hold
To clearly identify the
state transition of a
binary output relay,
the "new state" is
being hold, at least
for the duration of
the hold time.
0.00 - 300.00s
0.03s
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Latched
Defines whether the
Binary Output Relay
will be
acknowledged
automatically if the
event is gone or
whether the Binary
Output Relay is to be
acknowledged by a
signal/manually.
inactive,
active
BO Slot X2: active
BO Slot X5: inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Acknowledgment
Acknowledgment
Signal - An
acknowledgment
signal (that
acknowledges the
corresponding binary
output relay) can be
assigned to each
output relay. The
acknowledgment-
signal is only
effective if the
parameter "Latched"
is set to active.
Only available if:
Latched = active
1..n, Assignment List -
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Inverting
Inverting of the
Binary Output Relay.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Assignment 1
Assignment
1..n, Assignment List BO Slot X2: TripCmd
BO Slot X5: -
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Inverting 1
Inverting of the state
of the assigned
signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Page 140
EN MRA4 04/09
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...