Use these protectors on network cables that travel between buildings to
prevent damage to equipment, e.g. computers, servers, repeaters and hubs.
Suitable for computer networks up to Cat-6 cabling.

To protect up to 100baseT and up to 1000baseT networks with
Cat-5/Cat-5e cabling use ESP Cat-5e and ESP Cat-5e/Gb respectively

To protect up to 10GbaseT networks with Cat-6 cabling use ESP Cat-6

To protect up to 100baseT, 1000baseT and 10GbaseT Power over
Ethernet (PoE) networks use ESP Cat-5e/PoE, ESP Cat-5e/Gb/PoE and
ESP Cat-6/PoE respectively

For further application information, see separate

Application Note AN004

(contact us for a copy).

Furse, Wilford Road, Nottingham, NG2 1EB • Tel: +44 (0)115 964 3700 • Email: [email protected] • Web: www.furse.com

ESP Cat-5 & Cat-6 Series

NEW

Technical note

The interfaces used in Ethernet
networks incorporate an
isolation transformer which
gives these systems an inbuilt
immunity to transients
between line and earth of
1,500 Volts or more.

A Furse ESP Cat-5e/Gb protecting a hub from

transient overvoltages on a network

connection with another building

ELECTRONIC SYSTEMS PROTECTION

Plug-in Lightning Barrier

Wilford Road,
Nottingham,
NG2 1EB, UK

Plug-in series connection

DIRTY

CLEAN

From
line

To

equipment

Earth

Suitable for systems signalling on up to eight wires of either shielded
or unshielded twisted pair cable

Very low let-through voltage (enhanced protection to BS EN 62305)
between all lines - Full Mode protection

Full mode design capable of handling partial lightning currents as well
as allowing continual operation of protected equipment

Repeated protection in lightning intense environments

Unlike some competing devices, the ethernet SPDs provide effective
protection without impairing the system’s normal operation

Low capacitance circuitry prevents the start-up signal degradation
associated with other types of network protector

Low in-line resistance minimises unnecessary reductions in signal
strength to maximise signalling distance

Sturdy ABS housing with convenient holes for flat mounting, or
vertically via TS35 ‘Top Hat’ DIN rail

Substantial earth connection to enable effective earthing

Supplied with short (50 cm) Cat-5e UTP or Cat-6 STP cable to enable
neat installation

Features and benefits

Application

Combined Category D, C, B tested protector (to BS EN 61643)
suitable to protect twisted pair Ethernet networks, including
Power over Ethernet (PoE), with RJ45 connections. For use at
boundaries up to LPZ

0

B

to protect against flashover (typically the

service entrance location) through to LPZ 3 to protect sensitive
electronic equipment.

ESP CAT5e/UTP-1

1 metre cable with unshielded
RJ45 connections

ESP CAT6/STP-1

1 metre screened cable with
shielded RJ45 connections

Accessories

Connect in series with the network
cable, either:

a)

near to where it enters or
leaves the building, or

b) as it enters the network hub,

or

c)

close to the equipment being
protected

This should be close to the system’s
earth star point (to enable a good
connection to earth).

Installation