Tolerances
Frequency Protection f>[x]
Tolerance
f>
10 mHz at fn
resetting ratio
99.95%
or 0.05% fn
t
±1% resp.
±10 ms
Operating time
Starting from f higher than f>+0.02 Hz
40-50Hz <+60ms
50-70Hz <+50ms
Release time
40-50Hz <+85ms
50-70Hz <+75ms
Frequency Protection f<[x]
Tolerance
f<
10 mHz at fn
t
±1% resp.
±10 ms
resetting ratio
100.05% or 0.05% fn
Operating time
Starting from f lower than f<-0.02 Hz
40-50Hz <+60ms
50-70Hz <+50ms
Release time
40-50Hz <+85ms
50-70Hz <+75ms
V Block f
±1.5% of the setting value resp. 1% Un
resetting ratio
103%
or 0.5% x Un
Rate of Change of Frequency df/dt
Tolerance
df/dt
100 mHz per Second
t
±1% bzw.
±10 ms
Kommandozeit/
Anregezeit
<+40 ms
Rückfallzeit
<+40 ms
Vector surge delta phi
Tolerance
delta phi
±0,5° [1-30°] at Vn and fn
Operating time
<+40 ms
Circuit Breaker Failure Protection CBF
Tolerance
I-CBF>
±1.5% of the setting value resp.1% In
resetting ratio
t-CBF
±1% resp.
±10 ms
Operating time
Starting from I higher than 1.3 x I-CBF>
<+40 ms
Release time
<+40 ms
Page 506
EN MRA4 04/09
Summary of Contents for SEG HighPROTEC MRA4
Page 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Page 3: ...Order Code EN MRA4 04 09 Page 3...
Page 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Page 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Page 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...