Quick Start Guide

RE

www.tele-online.com

090 850

NA003

Part No.: 2700000

Danger! Never carry out work on live parts!  

Danger of fatal injury!  

The product must not be used in case of obvious damage!  

To be installed by an authorized person only!

• 

The full operation manual is available at: 

https://www.tele-online.com/resources/data-sheets/en_na003-m64.pdf

• 

This Quick Start Guide does not replace the manual and the owner should read in  

conjunction with the whole Manual.

• 

The safety instructions are to be observed

Intended use: 

The TELE NA003-M64 is a multinational grid and system protection unit, that protects energy generation 

plants ( like combined heat and power plants, wind generators, waterpower plants, photovoltaic plants).

In case of power failures or net anomalies, power gererating plants have to be disconnected immediately 

from the mains supply to avoid unintentional feeding to the grid. On the one hand continuing grid 

feeding could endanger maintenance staffs, on the other hand connected devices could be exposed to 

inadmissible voltages and/or frequencies.

In case the grid operator requires thresholds and settings that are not conforming with the local  standards, 

it is possible to set thresholds outside the normative defined range!

Outside these range the device is not in accordance with the standards anymore and the corresponding 

certificate loses validity! This state is indicated as „ncnf“ [none conformity] on the display.

Settings outside the conformity range are therefore in responsibility of the operator respectively the 

acceptance authority!

Dimensions:

62 mm

48,3 mm

25,5 mm

90,5 mm

106,3 mm

45 mm

62,4 mm

1

2

3

4

5

6

7

Controls elements:
Legend

Marking

Type

Function

1

R1, R2, R3

LED (yellow)

Status indication output relays

2

ENT

Pushbutton

ENTER, Input confirmation, menu level forward

3

ESC

Pushbutton

ESCAPE, Input rejection, menu level back, test/reset

4

-

Pushbutton

Change parameters, menu navigation

5

+

Pushbutton

Change parameters, menu navigation

6

PROG

Pushbutton (sealable)

PROGRAM, enter program mode

7

LCD-Display 4x20 

characters

Display

Terminals:

A1, A2

Supply

DC: 24V 

AC: 110 - 230V  @ f: 48-63 Hz

A1: L  (+)

A2: N  (-)

L1, L2, L3, N Measuring input

U

N

: 3x400V AC

11, 12, 14

Relay channel A (CO contact)

Status indication via yellow LED R1

Isolated changeover contact

11: Common 

12: Normally closed contact

14: Normally open contact

21, 22, 24

Relay channel B (CO contact)

Status indication via yellow LED R2

Isolated changeover contact

21: Common 

22: Normally closed contact

24: Normally open contact

31, 32, 34

Relay channel D (CO contact)

Status indication via yellow LED R3

Isolated changeover contact

31: Common 

32: Normally closed contact

34: Normally open contact

I1, 

Digital input 1 

(Feedback contact contactor A)

Contact input (24V/5mA), configurable

Input active: I1 connected to 

I2, 

Digital input 2 

(Feedback contact contactor B)

Contact input (24V/5mA), configurable

Input active: I2 connected to 

 

Does not apply to national standards without 

functional safety!

I3, 

Digital input 3 

(Remote disconnection)

Contact input (24V/5mA), configurable

Input active: NO->I3 to 

┴ 

(std); NC->I3 open

I4, I5, 

 

Digital inputs 4 und 5

(Parameter switchover)

Applies to CEI 0-21

Contact input (24V/5mA)

Input active: I4 or I5  connected to 

Technical data:

Supply circuit

Supply voltage: 

 

 

DC: 24V   

AC: 110 - 230V 

Supply voltage tolerance: 

 

DC: ± 10%  

AC: ± 30%

Nominal consumption: 

 

max. 1,25W / 4VA @ 230V AC

Rated frequency: 

 

 

50 / 60Hz 

Tolerance of rated frequency:   

48 - 63Hz

Rated surge voltage:  

 

6 kV

Internal protection:   

 

250V / 500mA slow blow (soldered)

In order to ensure the proper function during power failures, an external UPS has to be used.

Measuring circuit

Measuring input: 

 

 

3 x 400V AC

Input impedance:   

 

1MΩ

Measurand: 

 

 

line to line voltage, line to neutral voltage,

  

 

 

 

10 minutes average voltage, frequency, 

 

 

 

 

rate of change of frequency (RoCoF), phase shift (PShift)

Measuring ranges

Line to line voltage:    

 

0 - 560VAC 

Line to neutral voltage: 

 

0 - 325VAC

Frequency: 

 

 

40 - 65Hz

RoCoF:    

 

 

100mHz/s … 2.000mHz/s

Pshift:  

 

 

 

1 - 15°

Overload capacity:   

 

Permanent 1,4 x U

Nom

 

Pulse 1,6 x U

Nom

 (1 second)

Overvoltage category: 

 

III

Rated surge voltage:  

 

4 kV

Digital inputs

Type of contact: 

 

 

Isolated,  max.  wire  length  <30m,  control  wiring  standards 

 

                                                                          to be taken in account. The 

┴ 

are not connectied to each other.  

Min. switching voltage/ switching current:  24V DC / 5mA

Output circuit

Number of contacts:  

 

3 changeover contacts

Contact 

material: 

  AgNi

Rated current: 

 

 

5A / 250V AC

Electrical endurance: 

 

100 x 10

3

 switching cycles (AC-1)

Mechanical endurance: 

 

15 x 10

6

 switching cycles

Continous current value: 

 

5A

Short time value (1s): 

 

5A

Withstanding voltage across open contacts: 

Relay contacts: 1000V

rms

 

Terminals: 450V

rms

Overvoltage category: 

 

III

Rated surge voltage:  

 

4 kV 

 

 

Protection: 

 

 

5A fast blow

Accuracy

Voltage monitoring:

  

Base accuracy: 

 

< 0,5% @ +25°C 

 

Temperature influence: 

< 0,01% / °C

  

Resolution: 

 

10mV

Frequency monitoring: 

  

Base accuracy: 

 

< 0,01Hz @ +25°C 

 

Temperature influence: 

< 0,0002Hz / °C

  

Resolution: 

 

1mHz

Isolation data

Rated insulation voltage: 

 

400V

Supply circuit / Measuring circuit: 

protective insulation

Supply circuit / Output circuit:   

protective insulation

Supply circuit / Digital inputs:   

protective insulation

Output circuit / Measuring circuit: 

basic insulation

Output circuit / Digital inputs:   

basic insulation 

   

Environmental conditions

Ambient temperature operation: 

-25 … +55°C 

Ambient temperature storage:  

-40 … +70°C

Visibility temperature display:   

-15 … +55°C

Relative humidity:   

 

5 … 95% (non-condensing)

Pollution 

degree: 

  2   

Weight:   

 

 

300g

Electrical connection

Wire size:  

 

 

max. 2,5mm

2

Stripping length: 

 

 

max. 8mm

Electrical strength:   

 

max. 450V/16A (digital inputs; relay outputs)

  

 

 

 

max. 750V/16A (measuring inputs)

Torque:   

 

 

max. 0,5Nm

Screw: 

 

 

 

M3, slot screwdriver 0,6 x 3,5mm

Protection class 

 

 

Terminals: IP20 

Housing: IP20

Seal wire

   

 

 

max. diameter <=1,32mm

Safety advice: 

The device was developed, produced and tested in accordance to the latest industry standards.  

Nevertheless improper handling or use can endanger humans and machines.

Please use the device only in accordance with the installation and operating instructions. Check for secure 

assembly and good condition. Moreover, the rules and regulations on accident prevention applicable to 

the place of use must be strictly followed.

• 

Eliminate all faults immediately which may endanger safety!

• 

Do not make any unauthorised changes and only use replacement parts and optional  

 

 

accessories purchased from or recommended by TELE!

• 

In case of obvious damage the device must be checked and replaced if necessary!

• 

Country specific regulations have to be considered in any case!

• 

If required by national standards, the NA003 has to be protected against unauthorized  

 

 

changes by password and/or sealing!

Mounting on DIN rail according to EN 60715: 

Snap the rear mounting clip of the device into place in such a way that a safe and tight fit is ensured.

Available configurations/Local standards:

 

CEI 0-21:2019, VDE 0126-1-1:2013, VDE 0124-100:2013, VDE 4105:2018 <50kW, VDE 4105:2018 >50kW, 

VDE 4105:2018 Umr, G59/3/3:2015 LV, G99/1/3:2018 LV, G59/3/3:2015 MV, G99/1/3:2018 HV, G83/2:2012, 

G98/1/2:2018, C10-11:2012 LV, C10-11:2019 LV-IP, C10-11:2019 LV-ASS, C10-11:2012 MV, C10-11:2019 HV-IP,  

C10-11:2019 HV-ASS, TR3 Rev23:2013, VDE 4110:2018 TR3-25, OVE E 8001/8101:2014, OVE TOR R25 NS SYNC, 

OVE TOR R25 NS ASYNC, OVE TOR R25 MS SYNC, OVE TOR R25 MS ASYNC, OOE TOR R25 NS SYNC, OOE TOR R25 

NS ASYNC, OOE TOR R25 MS SYNC, OOE TOR R25 MS ASYNC, EN50438:2013, EN50438:2013 DK,  

NRS 097-2-1:2017, AS/NZS 4777.2:2015, OPEN SETUP

NA003-M64

Part No.: 2700100

doc no.: 090750