Switchgear/Breaker – Manager
Control Parameters
Ctrl
Direct Commands of the Control Module
Parameter
Description
Setting range
Default
Menu path
Switching Authority Switching Authority
None,
Local,
Remote,
Local and Remote
Local
[Control
/General settings]
NonInterl
DC for Non-Interlocking
inactive,
active
inactive
[Control
/General settings]
Global Protection Parameters of the Control Module
Parameter
Description
Setting range
Default
Menu path
Res NonIL
Resetmode Non-Interlocking
single Operation,
timeout,
permanent
single Operation [Control
/General settings]
Timeout NonIL
Timeout Non-Interlocking
Only available if: Res NonIL<>permanent
2 - 3600s
60s
[Control
/General settings]
NonIL Assign
Assignment Non-Interlocking
1..n, Assignment
List
-.-
[Control
/General settings]
Control Moduel Input States
Name
Description
Assignment via
NonInterl-I
Non-Interlocking
[Control
/General settings]
357
MRU4