Protective Elements
Setting Group Parameters of the Module External Protection
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/ExP
/ExP[1]]
502
MRU4
DOK-HB-MRU4-2E