Protective Elements
Parameter
Description
Setting range
Default
Menu path
V(t4)
Voltage value of a point V(t(n)). These points define the
LVRT profile.
0.00 - 1.50Vn
0.70Vn
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/LVRT Profile]
t4
Point in time for the corresponding voltage value
V(t(n)). These points define the LVRT profile.
0.00 - 20.00s
0.70s
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/LVRT Profile]
V(t5)
Voltage value of a point V(t(n)). These points define the
LVRT profile.
0.00 - 1.50Vn
0.90Vn
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/LVRT Profile]
t5
Point in time for the corresponding voltage value
V(t(n)). These points define the LVRT profile.
0.00 - 20.00s
1.50s
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/LVRT Profile]
V(t6)
Voltage value of a point V(t(n)). These points define the
LVRT profile.
0.00 - 1.50Vn
0.90Vn
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/LVRT Profile]
t6
Point in time for the corresponding voltage value
V(t(n)). These points define the LVRT profile.
0.00 - 20.00s
3.00s
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/LVRT Profile]
V(t7)
Voltage value of a point V(t(n)). These points define the
LVRT profile.
0.00 - 1.50Vn
0.90Vn
[Protection Para
/<1..4>
/Intercon-Prot
/LVRT[1]
/LVRT Profile]
486
MRU4