Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 15
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 15
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 16
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
Scale Factor 16
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 16
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 17
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
243
MRU4