Protective Elements
Parameter set parameters of the asymmetry module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/stage. This parameter is only effective if a
signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/stages are blocked that are parameterized
"ExBlo TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
V1>
Positive Phase Sequence Overvoltage
Only available if: Device planning: V012.Mode = V1>
0.01 - 1.50Vn
1.00Vn
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
V1<
Positive Phase Sequence Undervoltage
Only available if: Device planning: V012.Mode = V1<
0.01 - 1.50Vn
1.00Vn
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
V2>
Negative Phase Sequence Overvoltage
Only available if: Device planning: V012.Mode = V2>
0.01 - 1.50Vn
1.00Vn
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
%(V2/V1)
The %(V2/V1) setting is the unbalance trip pickup
setting. It is defined by the ratio of negative sequence
voltage to positive sequence voltage (%
Unbalance=V2/V1). Phase sequence will be taken into
account automatically.
inactive,
active
inactive
[Protection Para
/<1..4>
/V-Prot
/V012[1]]
428
MRU4
DOK-HB-MRU4-2E