Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 31
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 31
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Inputs of the DNP
Name
Description
Assignment via
BinaryInput0-I
Virtual Digital Input (DNP). This corresponds to a virtual binary
output of the protective device.
[Device Para
/DNP3
/Point map
/Binary Inputs]
BinaryInput1-I
Virtual Digital Input (DNP). This corresponds to a virtual binary
output of the protective device.
[Device Para
/DNP3
/Point map
/Binary Inputs]
BinaryInput2-I
Virtual Digital Input (DNP). This corresponds to a virtual binary
output of the protective device.
[Device Para
/DNP3
/Point map
/Binary Inputs]
BinaryInput3-I
Virtual Digital Input (DNP). This corresponds to a virtual binary
output of the protective device.
[Device Para
/DNP3
/Point map
/Binary Inputs]
BinaryInput4-I
Virtual Digital Input (DNP). This corresponds to a virtual binary
output of the protective device.
[Device Para
/DNP3
/Point map
/Binary Inputs]
251
MRU4
DOK-HB-MRU4-2E