Protective Elements
Device Planning Parameters of the Frequency Protection Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
f<,
f>,
f< and df/dt,
f> and df/dt,
f< and DF/DT,
f> and DF/DT,
df/dt,
delta phi
f[1]: f<
f[2]: f>
f[3]: do not use
f[4]: do not use
f[5]: do not use
f[6]: do not use
[Device planning]
Global Protection Parameters of the Frequency Protection Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/f-Prot
/f[1]]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/f-Prot
/f[1]]
ExBlo TripCmd
External blocking of the Trip Command of the
module/the stage, if blocking is activated (allowed)
within a parameter set and if the state of the assigned
signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/f-Prot
/f[1]]