General Lists
Name
Description
SG[1].t-Dwell
Signal: Dwell time
SG[1].Removed
Signal: The withdrawable circuit breaker is Removed
SG[1].Interl ON
Signal: One or more IL_On inputs are active.
SG[1].Interl OFF
Signal: One or more IL_Off inputs are active.
SG[1].CES succesf
Signal: Command Execution Supervision: Switching command executed successfully.
SG[1].CES Disturbed
Signal: Command Execution Supervision: Switching Command unsuccessful. Switchgear in disturbed
position.
SG[1].CES Fail TripCmd
Signal: Command Execution Supervision: Command execution failed because trip command is pending.
SG[1].CES SwitchDir
Signal: Command Execution Supervision respectively Switching Direction Control: This signal becomes
true, if a switch command is issued even though the switchgear is already in the requested position.
Example: A switchgear that is already OFF should be switched OFF again (doubly). The same applies to
CLOSE commands.
SG[1].CES ON d OFF
Signal: Command Execution Supervision: On Command during a pending OFF Command.
SG[1].CES SG not ready
Signal: Command Execution Supervision: Switchgear not ready
SG[1].CES Fiel Interl
Signal: Command Execution Supervision: Switching Command not executed because of field interlocking.
SG[1].CES SyncTimeout
Signal: Command Execution Supervision: Switching Command not executed. No Synchronization signal
while t-sync was running.
SG[1].CES SG removed
Signal: Command Execution Supervision: Switching Command unsuccessful, Switchgear removed.
SG[1].Prot ON
Signal: ON Command issued by the Prot module
SG[1].TripCmd
Signal: Trip Command
SG[1].Ack TripCmd
Signal: Acknowledge Trip Command
SG[1].ON incl Prot ON
Signal: The ON Command includes the ON Command issued by the Protection module.
SG[1].OFF incl TripCmd
Signal: The OFF Command includes the OFF Command issued by the Protection module.
SG[1].Position Ind manipul
Signal: Position Indicators faked
SG[1].SGwear Slow SG
Signal: Alarm, the circuit breaker (load-break switch) becomes slower
SG[1].Res SGwear Sl SG
Signal: Resetting the slow Switchgear Alarm
SG[1].ON Cmd
Signal: ON Command issued to the switchgear. Depending on the setting the signal may include the ON
command of the Prot module.
SG[1].OFF Cmd
Signal: OFF Command issued to the switchgear. Depending on the setting the signal may include the OFF
command of the Prot module.
SG[1].ON Cmd manual
Signal: ON Cmd manual
SG[1].OFF Cmd manual
Signal: OFF Cmd manual
SG[1].Sync ON request
Signal: Synchronous ON request
SG[1].Aux ON-I
Module Input State: Position indicator/check-back signal of the CB (52a)
SG[1].Aux OFF-I
Module input state: Position indicator/check-back signal of the CB (52b)
SG[1].Ready-I
Module input state: CB ready
SG[1].Sys-in-Sync-I
State of the module input: This signals has to become true within the synchronization time. If not, switching
is unsuccessful.
SG[1].Removed-I
State of the module input: The withdrawable circuit breaker is Removed
SG[1].Ack TripCmd-I
State of the module input: Acknowledgement Signal (only for automatic acknowledgement) Module input
signal
SG[1].Interl ON1-I
State of the module input: Interlocking of the ON command
SG[1].Interl ON2-I
State of the module input: Interlocking of the ON command
590
MRU4
DOK-HB-MRU4-2E