Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 7
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 7
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 8
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
Scale Factor 8
The scale factor is used to convert the measured value
in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 8
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value 9
Analog value can be used to report values to the
master (DNP)
1..n, TrendRecList -.-
[Device Para
/DNP3
/Point map
/Analog Input]
239