Communication Protocols
Generation/Export of a device specific ICD file
Please refer to chapter ”IEC61850“ of the Smart view Manual.
Generation/Export of a SCD file
Please refer to chapter ”IEC61850“ of the Smart view Manual.
Substation configuration,
Generation of .SCD file (Station Configuration Description)
The substation configuration, i. e. connection of all logical nodes of protection and control devices, as well as switch
gear usually is done with a „Substation Configuration Tool“. Therefore the ICD files of all connected IEDs in the
IEC61850 environment have to be available. The result of the station wide “software wiring” can be exported in the
form of a SCD file (Station Configuration Description).
Suitable Substation Configuration Tools (SCT) are available by the following Companies:
H&S, Hard- & Software Technologie GmbH & Co. KG, Dortmund (Germany) (
www.hstech.de
).
Applied Systems Engineering Inc. (
www.ase-systems.com)
Kalki Communication Technologies Limited (
www.kalkitech.com
)
Import of the .SCD file into the device
Please refer to chapter ”IEC61850“ of the Smart view Manual.
IEC 61850 Virtual Outputs
Additionally to the standardized logical node status information up to 32 free configurable status information can be
assigned to 32 Virtual Outputs. This can be done in the menu [Device Para/IEC61850].
209
MRU4
DOK-HB-MRU4-2E