Protective Elements
Device Planning Parameters of the Synchrocheck Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
Global Protection Parameters of the Synchrocheck Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Sync]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Sync]
Bypass
The Synchrocheck will be bypassed if the state of the
assigned signal (logic input) becomes true.
1..n, DI-LogicList
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Sync]
CB Pos Detect
Criterion by which the Circuit Breaker Switch Position is
to be detected.
-.-,
SG[1].Pos
SG[1].Pos
[Protection Para
/Global Prot Para
/Intercon-Prot
/Sync]
CBCloseInitiate
Breaker Close Initiate with synchronism check from any
control sources (e.g. HMI / SCADA). If the state of the
assigned signal becomes true, a Breaker Close will be
initiated (Trigger Source).
1..n,
SyncRequestList
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Sync]
440
MRU4
DOK-HB-MRU4-2E