Input, Output and LED Settings
Device Parameters of the Binary Output Relays on OR-5 X
Parameter
Description
Setting range
Default
Menu path
Operating Mode
Operating Mode
Working current
principle,
Closed-circuit prin-
ciple
Working current
principle
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
t-hold
To clearly identify the state transition of a binary output
relay, the "new state" is being hold, at least for the
duration of the hold time.
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
t-Off Delay
Switch Off Delay
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Latched
Defines whether the Relay Output will be latched when
it picks up.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Acknowledgement Acknowledgement Signal - An acknowledgement signal
(that acknowledges the corresponding binary output
relay) can be assigned to each output relay. The
acknowledgement-signal is only effective if the
parameter "Latched" is set to active.
Only available if: Latched = active
1..n, Assignment
List
-.-
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Inverting
Inverting of the Binary Output Relay.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Assignment 1
Assignment
1..n, Assignment
List
SG[1].TripCmd
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Inverting 1
Inverting of the state of the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Assignment 2
Assignment
1..n, Assignment
List
-.-
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
81
MRU4
DOK-HB-MRU4-2E