2017717_b•en•2016-11-01
We reserve the right to make technical changes
49
WAREMA climatronic®
Schaltaktor 4M230 LS2 Tief
WAREMA climatronic®
Schaltaktor 4M230 LS2 Tief
F2
6,3 AT H
F1
6,3 AT H
F2
6,3 AT H
F1
6,3 AT H
M 1.
1
M 1.2.
1
M 1.2.
2
M 2.
1
M 2.2.
1
M 2.2.
2
M 3.
1
M 3.2.
1
M 3.2.
2
M 4.
1
M 4.2.
1
M 4.2.
2
M 1.
1
M 1.2.
1
M 1.2.
2
M 2.
1
M 2.2.
1
M 2.2.
2
M 3.
1
M 3.2.
1
M 3.2.
2
M 4.
1
M 4.2.
1
M 4.2.
2
L
N
PE
Power line
provided
by customer
230 V AC, 50 Hz,
13 A, 3 x 1.5 mm
2
L
N
PE
L
N
PE
Example: Interlocking
via window contact
Operation is enabled
when the window is shut.
This function must be
programmed accordingly.
Example:
Single
push button,
motor 1
S1
Example:
Group push
button, motor 2
and motor 3
Groups are built
by means of
"jumpering"
1
3
2
BK GY BN
GNYE
M∼
Motor 1
2 TE
N
PE
To next
bus device
Bus A
Bus B
0 V
Example: Group push
button, motor 7 and motor 8
Connection of group push
buttons at the locking inputs.
The locking function is no
longer available.
The relevant group is freely
programmable within an
actuator (see
WAREMA climatronic
®
Commissioning/Setting
instructions,
art. no. 2017718).
Example: group push
button, motor 5 and
motor 6
Groups are built for all
actuators by "jumpering".
Only connect In+ for the
actuators in the group.
Bus A
Bus B
0 V
Bus A
Bus B
0 V
In+
In+
From
previous
bus device
Bus A
Bus B
0 V
Motor 2
2 TE
Motor 3
2 TE
Motor 4
2 TE
Motor 5
2 TE
1
3
2
BU BK BN GNYE
Motor 6
Window
N
PE
1
3
2
BU BK BN
GNYE
M∼
Motor 7
Sun shading system
1
3
2
BU BK BN
GNYE
M∼
Motor 8
Sun shading system
N
PE
N
PE
ATTENTION:
Only one motor can be connected
per motor terminal set.
Parallel connection will
damage the motor.
The total power (of all 4 outputs)
per fuse must not exceed 1000 VA.
Motor lines for motors with 2 lower limit switches
H05-RR-F 5 G 0,75 bk
For Switzerland:
H05-RR-F 5 G 1,5 bk
or alternatively
LiHH 5x1,5 JZ gr 600/1000V flexible, halogen-free
(not UV resistant)
All push button lines
JY(St)Y 2x2x0.8 mm
Max. line length 200 m for
interference-proof routing,
use a twisted pair line.
All bus lines
JY(St)Y 4×2×0.8 mm
M∼
CLOSE
OPEN
4
BL
1 2
1
3
2
BK GY BN
GNYE
M∼
N
PE
4
BU
1 2
1
3
2
BK GY BN
GNYE
M∼
N
PE
4
BU
1 2
1
3
2
BK GY BN
GNYE
M∼
N
PE
4
BU
1 2
ATTENTION:
By use of standard drives without
2 lower limit switches, always use
Low 2 ( 2).
1
3
2
BK GY BN
GNYE
M∼
N
PE
4
BU
1 2
Motor lines for motors
with 1 lower limit switch
H05-RR-F 4 G 0,75 bk
Typ WAREMA
For Switzerland:
H05-RR-F 4 G 1,5 bk
Fig. 26
Connection example switch actuator 4M230 LS2 Low