2017717_b•en•2016-11-01
We reserve the right to make technical changes
62
WAREMA climatronic® 3.x
Installation and connection
10.2.6 24 V supply
Is there 24 V DC in contact with the weather station, control panel and,
if available, hub or actuators powered by other sources?
For multiple power supply units:
Do not connect power supply units in parallel.
+24 V DC wires separated into sensible subsections?
0 V wires of all devices and power supply units connected with each other?
10.2.7 Positioning of the weather station
Weather station correctly positioned on the building?
The photodiodes must be at right angles to the building facades being
shaded.
see also chapter 4.3 on page 13
Positioning
Facade/Compass direction
Photodiode 1
10.2.8 Function of the push buttons on the actuators
Do the single push buttons connected to the actuators?
When not programmed only 1 relay is activated in the actuator at a time
→ the single motor operations must function (motor only moves for as long
as the push button is activated).
Is the direction of rotation of the connected motors correct (UP / DOWN)?
Pho
to
1
(dawn / dusk)
Pho
to
3
Photo 4
Photo 2