4.4 Nnstall actuators
The actuators are available as a DIN rail-mounted device (REG) and in a
surface-mounted housing depending on the model. The devices must be
installed in a dry and easily accessible location. Never install them outdoors
or where they are subjected to direct solar radiation.
DATNIA
DIN rail-mounted devices must be mounted on a symmetrical DIN rail
(TH 35 as per EN 60715:2001) when installed in a distribution board.
DATNIA
The minimum distance between the connection terminals and another
object equals must be at least 10 mm in the DIN rail-mounted model. When
actuators are properly installed in the surface-mounted housing, then no
minimum distances need to be observed between the housing and the
surrounding objects.
R G
: When installing the device in a distribution board, clip it onto a
symmetrical DIN rail. To make the connection work easier, the terminal
covers can be removed (see Fig. 7).
AP
: Insert a slotted screwdriver (3 – 4 mm blade) into the appropriate
cover opening and carefully pry the hinged cover open. Repeat the
procedure for the second opening of the cover. After both latches
have been unlatched, the cover can be flipped open. Open the
second cover in the same way. Alternatively, the AP model may also
be mounted on a DIN rail.
This device type is not suitable for use in damp interiors.
Remove the terminal covers:
Insert a suitable screwdriver
into the notch.
Fig. 7
Detaching the terminal covers
Note the information in the associated operating and installation instructions
when installing the surface-mounted or DIN rail-mounted housing model.