We reserve the right to make technical changes
46
WAREMA climatronic® 3.x
Installation and connection
M
M
BN
BK
BU
2
M~
3
2
1
3
2
1
1
2 1
2 1
BK
BK
BN
RD
3
LIHCH 2x2x0,14 BK
1
3
2
BU BK BN
GNYE
M∼
Motor 5
Motor 6
Connection example
Motor with additional
incremental encoder
From
previous
bus device
Power line provided
by customer
230 V AC, 50 Hz,
16 A, 3 x 1.5 mm
2
PE
N
L
Schaltaktor
4M230I (vivamatic® 3.0)
1
3
2
BU BK BN
GNYE
M∼
Motor 1
**
F1
6,3 AT H
F2
6,3 AT H
ATTENTION
Only one motor can be connected
per motor terminal set.
Parallel connection will
damage the motor.
1
3
2
BU BK BN
GNYE
M∼
Motor 2
1
3
2
BU BK BN
GNYE
M∼
Motor 3
1
3
2
BU BK BN
GNYE
M∼
Motor 4
Bus A
Bus B
0 V
To next
bus device
S1
Bus A
Bus B
0 V
M
M
Schaltaktor
4M230I (vivamatic® 3.0)
F1
6,3 AT H
F2
6,3 AT H
Example:
Interlocking via window contact
Operation is enabled when the window is shut.
This function must be programmed
accordingly.
Example:
Group push button, motor 1 and motor 2
Connection of group push buttons at the
locking inputs. The locking function is no
longer available. The relevant group is freely
programmable within an actuator (see
WAREMA climatronic® installation
instructions)
Example:
Single push button, motor 1
Example:
group push button, motor 4 and
motor 5
Groups are built for all actuators
by "jumpering".
Only connect In+ for the actuators
in the group.
Bus connection "nc" = not connected (not
assigned)
The nc connection (yellow terminal) is not connected
to the device. The yellow terminal can be used to
connect through the 24 V wire for the following
devices that require 24 V.
**
**
Supply to motors:
The power supply to the motors can be
implemented via a jumper to the L-terminals
at terminal block X1.
Legend for other
climatronic
®
actuators:
In+ = P
In5 = V1
In6 = V2
In7 = V3
In8 = V4
In1 1.1 = E1.1
In1 1.2 = E1.2
...
ATTENTION
The operating voltage of the motors
must be identical to the operating
voltage of the actuator. The actuator
has no floating outputs.
Bus A
Bus B
0 V
Bus A
Bus B
0 V
PE
N
L
PE
N
L
All motor lines
H05-RR-F 4 G 0.75 black, type WAREMA
All push button lines, JY(St)Y 2x2x0.8 mm
Max. line length 200 m for
interference-proof routing,
use a twisted pair line.
All bus lines JY(St)Y 4×2×0.8 mm
In+
In+
Fig. 25
Connection example for switch actuator 4M230I (vivamatic® 3.0)