2017717_b•en•2016-11-01
We reserve the right to make technical changes
22
WAREMA climatronic® 3.x
Installation and connection
5.3.2 Local group push buttons
The local inputs (E1.1...E6.2) are available for the local operation of
individual products
Local group push buttons are only used for the joint local operation of
products with push buttons (product groups). They are independent from the
groups in the control panel that can be used to operate several channels
together via the control panel (channel groups).
The locking contact inputs V1...V6 (for the 4M actuator V1...V4 only) can be
used for the joint local operation of several products connected to the same
actuator as a local group.
Each locking contact can either be used for locking or as a group input for
a group push button, but not for both at the same time.
Only one single locking contact input is needed to lock a product.
A locking contact input can lock several products on the same actuator.
For building light and fan product groups, one locking contact is required
for each group; for building groups of the sun shading product and window
product types, two adjacent locking contacts are required as local group
inputs.
The group inputs can be allocated to several products on the same actuator.
The fault alarm contact can neither be disabled nor operated via group push
buttons.
To build local groups from products located on different actuators, the group
inputs of the products must be joined in the form of a group control line.
Appropriate examples can be found in the wiring diagrams.
DEANAN
Actuators with different power supplies must not be joined together to
build groups.
Building groups between 4/6M230 and 4/6M actuators is therefore not
possible.
To plan and document the inputs and outputs and the locking contacts,
use the tables on the last page of the actuator instructions.