5.3 onnecting switch actuator 4M230/6M230
The safety instructions from
section 5 Connection on page 16 a
lso
apply for connecting the actuators.
To prevent damage to the connected motors, the default settings are such
that only one relay is activated at a time and connected single push buttons
operate in dead man's mode. Group buttons and locking contacts are
functional after the actuator has been commissioned.
Detailed information on connecting can be found in the associated
installation instructions art. no. 890350.
Information and wiring diagrams for other actuators can be found
in
chapter 7 on page 33
:
7.1 Switch actuator 4M/6M AP/REG on page 34
7.2 Switch actuator 4MDC AP/REG on page 34
7.3 Switch actuator 16M230 SMI AP/REG on page 35
7.4 Switch actuator 4M230I (vivamatic® 3.0) AP/REG on page 36
7.5 Switch actuator 4M230 LS2 Low AP/REG on page 37
7.6 Dim actuator 2D AP/REG on page 38
5.3.1 Switch actuator outputs
ach controllable product requires 1 to 3 output terminals:
Sun shading products and windows use 2 adjacent outputs of a terminal
block and 2 inputs of the same number, e.g. A 1.1, A 1.2, E 1.1, E 1.2
Fans and lights use 1 output and 1 input of the same number, e.g. A 1.1,
E 1.1
Infinitely variable fans (external) and dimmable lights use 2 adjacent outputs
of a terminal block and 1 input with the same number as the first output, e.g.
E
3.2
, A
3.2
, A 4.1
Fans 6/12 V, 3-step fans and 3-step fans with valve use 3 adjacent outputs
of a terminal block and 1 input with the same number as the 1st output, e.g.
E
5.2,
A
5.2
, A 6.1, A 6.2
All outputs for one product are always located on the same terminal block.
In product management, each product can be allocated any locking contact
of the same actuator
.