10 Troubleshooting
10.1 Fault table
Problem
Possible cause
Remedy
No information in display
No 230 V on power supply unit
Switch on the in-line circuit breaker,
check the power supply
Power supply unit faulty
Replace power supply unit
Wrong connection
Correct connection
Switch actuators: when operating using
local push buttons only one product moves
The default settings are such that only one
relay is activated at a time and connected
single push buttons operate in dead man's
mode. Group buttons are functional after
the actuator is commissioned.
Completely commission the WAREMA
climatronic® system.
Actuator 16M230 SMI: when operating
using local push buttons all products move
In the default settings, the connected single
push buttons operate in dead man's mode;
activation of a single push button initiates
movements in all connected motors.
Group buttons and locking contacts are
functional after the actuator is commis-
sioned.
Completely commission the WAREMA
climatronic® system.