Reset plate
Type E548
X1
X2
5
Fig. 5.10: Fitting the rest board into the
TITANUS
MICRO · SENS
®
additional housing
Fitting
To fit the reset board into the TITANUS
MICRO·SENS
®
additional hous-
ing, the following steps must be taken:
1
Using a screwdriver, loosen the four screws on the additional
housing cover.
2
Put the terminating resistor 1 R
ER
as calculated into the connecting
terminal X1.
3
Fix the reset board to the installation board with 3 plastic spacers (for
fixing points see Fig. 5.8) in the additional housing.
4
The electrical connection (terminal strip 8a/b) is described in section
5.5.1.
5
Fix the cover on again by screwing down the four screws on the
device cover firmly using a screwdriver
.
1
Terminal resistor not supplied, performance 1/4W
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......