Commissioning
TITANUS
MICRO·SENS
®
7
– 18
Data: 01/09
MS_A_07-en-e
The aspiration point for which the transport time is to be determined is
now selected by clicking. For each aspiration point selected, the
pre-selected time required for reaching the aspiration point and providing
the smoke must be entered. When the pre-selected time has lapsed, the
particular smoke detection point must be charged with smoke. There
must be smoke at the aspiration point for another 10 to 15 seconds after
the pre-selected time has lapsed.
Before starting to determine the transport time, check by using a bar
graph (smoke level) that there is no smoke in the aspiration pipe.
?
TITANUS
MICRO · SENS
®
Assume
10
9
8
7
6
5
4
3
2
1
0
s
50,0
s
40,0
s
s
s
18,4
21,4
15,5
E
D
C
B
A
min
s
0
30
Start
00000
5
s
60,0
V
12,0
V
13,5
?
?
?
Smoke level
File Record
Settings
Device-Selection
(Date Time)
Fault messages
Status
Settings
ROOM-IDENT
Reception
Serial No.
Transp. time not established
Transport time established
Transport time invalid
Amount of aspiration points
Pre selection time
Measuring active
Training mode active
Establish transport time
Blow out time
Intake fan
Blow out fan
Cancel
After starting to determine the transport time, the learn mode is active
and
TITANUS
MICRO·SENS
®
switches to blowing out the aspiration pipe.
The display for the aspiration point in question is yellow.
After the pre-selected time has lapsed, the
TITANUS
MICRO·SENS
®
switches to aspirate. At this point, there must be smoke at the aspiration
point selected.
If the
TITANUS
MICRO·SENS
®
detects the smoke, the smoke level
indicates this. The display for the aspiration point selected goes green
and the time determined is entered.
The learn mode for the aspiration point selected is thereby closed.
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......